Instrumentation Cables 
BS5308 Cable ESI Cable BS 6231 Cable DEF Standard Cable EN50288-7 LSZH Cables EN50288-7 PVC Cables NF M 87-202

   NF M 87-202 EIFA

NF M 87-202 EIFA Instrumentation Cables

APPLICATION 
These NF M 87-202 EIFA instrumentation cables are used for safety extra-low use in petroleum and petrochemical units particularly for the transmission of a.c. or d.c. analogue signals, They are well adapted to underground use in industrial applications where hydrocarbons may be present and mechanical protections are needed (refinery areas, chemical plant…).

Standards References:
NF M 87-202
UTE C 32-014
NF C 32-020
IEC 60332-1
IEC 60332-3-24

CABLE CONSTRUCTION
Conductor:
Solid or Stranded copper conductor
Insulation:
PVC (70 mm maximum pair length)
Individual Binder Tape:
Polyster tape
Individual Screen:
Aluminium/polyester tape
Individual Sheath:
PVC
Overall Binder Tape :
Polyster tape
Collective Screen:
Aluminium/polyester tape
Inner Sheath: PVC
Amouring:
Double Steel Tape
Outer Sheath:
PVC (Flame retardant, sunlight, mineral oil and hydrocarton resistant)
Outer Sheath Colour:
Light-blue
Core identification:

Colours

Natural

Red

Blue

Yellow

1 pair

X

X

 

 

1 triple

X

X

X

 

1 quad

X

X

X

X

Characteristics
Voltage Rationg: 300/500V
Operating Temperature: -40°C/+90°C
Installation Temperature: MAX+50°C
Maximum Voltage: 250V
Voltage Test: 2000V
Maximum conductor d.c. Resistance:

Conductor Size

Ohm/km at +20°C

1/0.80mm(0.50 sqmm)

37.50

7/0.40mm(0.88 sqmm)

21.40

7/0.53mm(1.50 sqmm)

12.50

Capacitance between cond. (nf/km):
0.5 sqmm ≤ 145
0.88 sqmm ≤ 160
1.50 sqmm ≤ 180
Type/codification:

1 Serie

Number of pairs, triples or quads / 01 to 27

2 Serie

Lay up in pair(IP) ,triple (IT) , quads (IQ)

3 Serie

Core section 05 (0.5mm2) , 09 (0.88 mm2) or 15(1.5mm2)

4 Serie

Overall screen(EG) or individual screen + overall screen(EI)

5 Serie

Mechanical protection: without armour (SF), with armour (FA), with lead + armour(PF)

Natural cores printed with pair/triple number

Dimensions and Weight:

NF M 87-202

Number of
beams x cross section

Cond.
mm2

Outer Diameter(mm)

Weight
(kg/km)

 

 

 

Min.

Max.

 

03 IP 05 EIFA

3X2X0.50

0.50

14.20

16.20

355

07 IP 05 EIFA

7X2X0.50

0.50

18.60

21.40

570

12 IP 05 EIFA

12X2X0.50

0.50

23.30

26.70

850

19 IP 05 EIFA

19X2X0.50

0.50

28.10

32.30

1210

27 IP 05 EIFA

27X2X0.50

0.50

32.80

37.60

1600

03 IP 09 EIFA

3X2X0.88

0.88

18.50

20.40

465

07 IP 09 EIFA

7X2X0.88

0.88

22.90

25.30

792

12 IP 09 EIFA

12X2X0.88

0.88

29.00

32.00

1205

19 IP 09 EIFA

19X2X0.88

0.88

34.80

38.40

1709

27 IP 09 EIFA

27X2X0.88

0.88

40.60

44.80

2275

03 IP 09 EIFA

3X2X0.88

0.88

16.70

19.20

270

07 IP 09 EIFA

7X2X0.88

0.88

22.40

25.70

800

12 IP 09 EIFA

12X2X0.88

0.88

28.10

32.30

1185

19 IP 09 EIFA

19X2X0.88

0.88

34.10

39.10

1720

27 IP 09 EIFA

27X2X0.88

0.88

39.80

45.70

2285

01 IP 15 EIFA

1X2X1.50

1.50

10.20

11.70

200

07 IT 05 EIFA

7X3X0.50

0.50

20.30

23.30

690

12 IT 05 EIFA

12X3X0.50

0.50

25.40

28.00

1005

12 IT 09 EIFA

12X3X0.88

0.88

25.00

28.70

1025

01 IT 15 EIFA

1X3X1.50

1.50

10.50

12.00

220